SLC 500 to ControlLogix: Instruction Set Conversion Table

Conversion reference for Allen-Bradley SLC 500 instructions to ControlLogix/CompactLogix equivalents. Covers addressing, data types, timers, counters, math, and file instructions.

·10 min read
Allen-BradleySLC 500ControlLogixCompactLogixinstructionconversionmigrationRSLogixStudio 5000

SLC 500 to ControlLogix: Instruction Set Conversion Table

When migrating from Allen-Bradley SLC 500 (RSLogix 500) to ControlLogix or CompactLogix (Studio 5000 Logix Designer), most instructions have direct equivalents — but the addressing system is fundamentally different. This reference covers the key instruction and addressing changes.

Addressing System Change

This is the single biggest difference between SLC 500 and ControlLogix:

ConceptSLC 500 (RSLogix 500)ControlLogix (Studio 5000)
AddressingFile-based: N7:0, B3:0/0, T4:0Tag-based: MyInteger, MyBool, MyTimer
I/OFixed slot: I:1/0, O:2/0Module path: Local:1:I.Data[0]
Integers16-bit INT: N7:0 (-32768 to +32767)32-bit DINT (default)
Data filesNumbered: N7, B3, T4, C5, R6, F8Named tags: any descriptive name
Bit addressingB3:0/0MyBoolArray[0].0 or named BOOL tag

Migration trap: SLC 500 uses 16-bit integers (INT). ControlLogix defaults to 32-bit DINT. Arithmetic involving negative numbers or bit manipulation may behave differently. The Logix Designer Export tool creates "SLC-Type" tags that preserve the 16-bit behavior, but these should be converted to native DINT tags for optimal performance.

Instruction Mapping

Bit Instructions

SLC 500ControlLogixNotes
XIC (Examine If Closed)XICIdentical
XIO (Examine If Open)XIOIdentical
OTE (Output Energize)OTEIdentical
OTL (Output Latch)OTLIdentical
OTU (Output Unlatch)OTUIdentical
OSR (One-Shot Rising)ONSName changed, same function

Timer/Counter Instructions

SLC 500ControlLogixNotes
TON (Timer On Delay)TONSame — but timer structure changes
TOF (Timer Off Delay)TOFSame
RTO (Retentive Timer On)RTOSame
RES (Reset)RESSame
CTU (Count Up)CTUSame
CTD (Count Down)CTDSame

Timer structure change: SLC 500: T4:0.ACC, T4:0.PRE, T4:0.DN. ControlLogix: MyTimer.ACC, MyTimer.PRE, MyTimer.DN. Same fields, tag-based names.

Math Instructions

SLC 500ControlLogixNotes
ADDADDSame — but watch INT→DINT overflow
SUBSUBSame
MULMULSame
DIVDIVSame — ControlLogix DIV can return REAL
NEGNEGSame
SQRSQRSame
CPT (Compute)CPTSame — more powerful in ControlLogix

Comparison Instructions

SLC 500ControlLogixNotes
EQUEQUSame
NEQNEQSame
GRTGRTSame
GEQGEQSame
LESLESSame
LEQLEQSame
LIM (Limit Test)LIMSame

Move/Copy Instructions

SLC 500ControlLogixNotes
MOV (Move)MOVSame
COP (Copy File)COPSame — tag-based addressing
FLL (Fill File)FLLSame
MVM (Masked Move)MVMSame

File/Array Instructions

SLC 500ControlLogixNotes
FAL (File Arithmetic/Logic)FALSame — uses tag arrays instead of file numbers
FSC (File Search/Compare)FSCSame
COP with file #COP with array tagAddress syntax changes

Communication

SLC 500ControlLogixNotes
MSG (Message)MSGRestructured — EtherNet/IP replaces DH+/DH485
DH+ protocolEtherNet/IP (CIP)Network change required
DH485EtherNet/IPDH485 is obsolete

Instructions NOT Available in SLC 500

ControlLogix adds instructions not available in SLC 500: AOI (Add-On Instructions) for reusable code, PIDE (PID Enhanced), MOD (Modulo), structured text in rungs, UDTs (User-Defined Types), PHASE/EQUIPMENT for ISA-88, and CIP Motion instructions.

Frequently Asked Questions

Does the Logix Designer Export tool convert everything automatically?

No. The tool converts ladder logic only — not SFC or Structured Text. It produces SLC-Type tags that need manual cleanup. I/O configuration must be remapped manually. The tool saves hundreds of hours but is not a complete solution.

Can I keep my SLC 500 I/O modules with a ControlLogix processor?

Not directly. SLC 500 (1746) I/O is not compatible with ControlLogix (1756) backplanes. You need 1756-series I/O modules or a 1756-SYNCH bridge module for legacy integration.


Analyze Your Allen-Bradley Code

PLCcheck Pro supports Allen-Bradley SLC 500 and PLC-5 program analysis. Upload your .RSS or .RSP file for documentation and migration guidance.

Upload AB code for analysis →

Part of the Allen-Bradley Reference. Maintained by PLCcheck.ai. Not affiliated with Rockwell Automation.